In older existing installations, where an equipment ground does not exist in a metal switch box that is located within reach of a conductive floor such as tile or cement, NEC 404.9 (B) requires the use of what kind of faceplate

+4
Answers (2)
  1. 25 January, 15:11
    0
    A metal faceplate with grounding means

    Explanation:

    metal faceplate with grounding means is required in older existing installations, where an equipment ground does not exist in a metal switch box that is located within reach of a conductive floor such as tile or cement.
  2. 25 January, 16:46
    0
    The NEC requires the use of a metallic faceplate for this situation.

    Explanation:

    NEC 404.9 (B) requires a metal faceplate having a means for grounding to be used in older installations where there is no ground for an equipment in a metal box switch located within a conductive floor. There is however an exception which states that as long as the wiring method does not have anything to do with an equipment-grounding conductor, it is required that a snap switch that is wired and located within reach of conductive floors must have a nonmetal faceplate or protected by an interrupter.
Know the Answer?
Not Sure About the Answer?
Find an answer to your question ✅ “In older existing installations, where an equipment ground does not exist in a metal switch box that is located within reach of a ...” in 📘 Computers and Technology if you're in doubt about the correctness of the answers or there's no answer, then try to use the smart search and find answers to the similar questions.