Question 7 options: A steel tape that has a length of 100.00 at 68 degrees F is to be used to lay off a building with the dimensions 450.00 ft by 515.00 ft. What should the tape readings be if the tape temperature is 104 degrees F at the time of measurement

+2
Answers (1)
  1. 2 May, 07:02
    0
    The tape readings at 104°F will be 449.88 ft by 514.86 ft

    Explanation:

    Co-efficient of linear expansivity of Steel = α = 7.3 * 10⁻⁶ ft/ft.°F (from literature)

    α = ΔL / (L₀ (ΔT)

    ΔL = change in length = ?

    L₀ = original length = 100.0 ft

    ΔT = change in temperature = 104 - 68 = 36°F

    ΔL = α * (L₀ (ΔT))

    ΔL = 7.3 * 10⁻⁶ * 100 * 36 = 0.02628 ft = 0.0263 ft

    ΔL = Lf - L₀

    Lf = L₀ + ΔL = 100 + 0.0263 = 100.0263 ft

    This tape is used to measure a dimension of 450 ft * 515 ft,

    Meaning, the 450 ft will give a reading of 450 * 100/100.0263 = 449.88 ft

    And the 515 ft gives a reading of 515 * 100/100.0263 = 514.86 ft.

    The tape readings at 104°F will be 449.88 ft by 514.86 ft
Know the Answer?
Not Sure About the Answer?
Find an answer to your question ✅ “Question 7 options: A steel tape that has a length of 100.00 at 68 degrees F is to be used to lay off a building with the dimensions 450.00 ...” in 📘 Engineering if you're in doubt about the correctness of the answers or there's no answer, then try to use the smart search and find answers to the similar questions.