A heat pump operates on the ideal vapor-compression refrigeration cycle and uses refrigerant-134a as the working fluid. The condenser operates at 1000 kPa and the evaporator at 200 kPa. Determine this system's COP and the rate of heat sup - plied to the evaporator when the compressor consumes 6 kW.

+2
Answers (1)
  1. 3 December, 17:56
    0
    QL = 24.51 kW

    COP = 5.085

    Explanation:

    h₁ = 244.5 kj / kg, h₂ = 278.07 kj / kg, h₃ = h₄ = 107.34 kj / kg

    P₁ = 1000 kPa, P₂ = 200 kPa

    W = 6 kW

    To determine the rate heat can use the equation

    QL = m * (h₁ - h₄)

    QL = W * (h₁ - h₄) / (h₂ - h₁)

    QL = 6 * (244. 5 - 107.34) / (278.07 - 244.5)

    QL = 24.51 kW

    To determine the COP is the rate hate relation with the work done

    COP = QH / W

    COP = 1 + QL / Q

    COP = 1 + [ 24.51 kW / 6 kW ]

    COP = 5.085
Know the Answer?
Not Sure About the Answer?
Find an answer to your question ✅ “A heat pump operates on the ideal vapor-compression refrigeration cycle and uses refrigerant-134a as the working fluid. The condenser ...” in 📘 Engineering if you're in doubt about the correctness of the answers or there's no answer, then try to use the smart search and find answers to the similar questions.