Several 4-conductor cables are installed in a ladder cable tray without a cover and without exceeding the cable tray fill limit. Each 4-conductor cable comprises four 1/0 AWG THHN copper conductors, each of which is considered current-carrying. What is the allowable ampacity of each 1/0 AWG THHN copper conductor?

+5
Answers (1)
  1. 20 June, 17:16
    0
    Answer: The allowable ampacity is 136 amperes

    Explanation:According to the National Electrical Code the ampacity for insulated conductors of type 1/0 AWG THHN is 170 amperes (from tables) for cables no exceeding 3

    But we are presented with 4 cables in a tray,

    Going by the National Electrical Code where conductors exceeds 3, the allowable ampacity shall be reduced to 80% the of the ampacity gotten from table.

    Hence the allowable ampacity for 4 copper cables of type 1/0 AWG THHN is (80/100) * 170=136 Amperes
Know the Answer?
Not Sure About the Answer?
Find an answer to your question ✅ “Several 4-conductor cables are installed in a ladder cable tray without a cover and without exceeding the cable tray fill limit. Each ...” in 📘 Physics if you're in doubt about the correctness of the answers or there's no answer, then try to use the smart search and find answers to the similar questions.
Search for Other Answers