A balanced three-phase inductive load is supplied in steady state by a balanced three-phase voltage source with a phase voltage of 120Vrms. The load draws a total of 10kW at a power factor of 0.9. Calculate the rms values of the phase currents and the magnitude of per-phase load impedance, assuming a wye-connected load. Draw a phasor diagram showing all three voltages and currents.

+4
Answers (1)
  1. 22 July, 16:21
    0
    Answer: Voltage, V=120V; Power, P=10kW or 10,000W

    P = V*I (where I is current)

    ∴ I = P/V = 10000/120 = 83.3A

    Resistance, R = V/I = 1.44 ohms

    Power Factor (cosФ) = 0.9 = Resistance, R/Impedance, Z

    ∴ Z = 1.44/0.9 = 1.6 ohms

    Explanation: The three-phase inductive load supply carries alternating current of the same frequency and voltage amplitude relative to a common reference but phase difference of one third of a cycle between each of three voltages and currents.
Know the Answer?
Not Sure About the Answer?
Find an answer to your question ✅ “A balanced three-phase inductive load is supplied in steady state by a balanced three-phase voltage source with a phase voltage of 120Vrms. ...” in 📘 Physics if you're in doubt about the correctness of the answers or there's no answer, then try to use the smart search and find answers to the similar questions.