A NATO base in northern Norway is warmed with a heat pump that uses 7.0 °C ocean water as the cold reservoir. Heat extracted from the ocean water warms fluid to 80°C; this warmed fluid is used to heat the building. When the system is working at full capacity, 2,000 kW of heat is delivered to the building at the cost of 600 kW of electric energy. a. What is the actual coefficient of performance of the system? b. What is the theoretical maximum coefficient of performance of the system?

+2
Answers (1)
  1. 23 June, 15:40
    0
    3.33, 4.84

    Explanation:

    A) Actual coefficient of performance can be calculated by the formula stated below

    Actual COP = heat delivered / work required

    Actual COP = 2,000/600

    Actual COP = 3.33

    B) Th = High temperature = 80°C + 273 = 353K

    Tl = Low temperature = 7°C + 273 = 280K

    The theoretical maximum coefficient of performance can ve calculated by the formula

    Theoretical COP = Th / (Th-Tl)

    Theoretical COP = 353 / (353-280)

    Theoretical COP = 353/73

    Theoretical COP = 4.84
Know the Answer?
Not Sure About the Answer?
Find an answer to your question ✅ “A NATO base in northern Norway is warmed with a heat pump that uses 7.0 °C ocean water as the cold reservoir. Heat extracted from the ocean ...” in 📘 Physics if you're in doubt about the correctness of the answers or there's no answer, then try to use the smart search and find answers to the similar questions.