In later years, motors improved and could be run directly from a 60 Hz power supply. As a result, 25 Hz power systems shrank and disappeared. However, there were many perfectly-good working 25 Hz motors in factories around the country that owners were not ready to discard. To keep them running, some users created their own 25 Hz power in the plant using motor-generator sets. A motor generator set consists of two machines connected on a common shaft, one acting as a motor and the other acting as a generator. If the two machines have different numbers of poles but exactly the same shaft speed, then the electrical frequency of the two machines will be different due to Equation (3-34). What combination of poles on the two machines could convert 60 Hz power to 25 Hz power?

+4
Answers (1)
  1. 12 December, 21:30
    0
    as in motor generaror are connected to same shaft then both machines are working with same speed

    but number of poles are different with same speed means both machines are working with different frequencies

    we know

    frequency F = N*P/120

    speed N = 82120F/P

    given

    motor speed = generator speed

    120F1/P1 = 120F2/P2

    F1/P1 = F2/P2

    output frequency is 25 which is obtained from generator so F2=25

    input frequency is 60 which is given to motor soF1=60

    60/P1 = 25/P2

    60/25 = P!/P2

    P1/P2 = 12/5

    multiply and divided by 2 becuase poles are even

    P1/P2 = 12*2/5*2

    =24/10

    P1 = 24 poles a

    P2 = 10 poles we get 25 hz frequency from 60 hz frequency
Know the Answer?
Not Sure About the Answer?
Find an answer to your question ✅ “In later years, motors improved and could be run directly from a 60 Hz power supply. As a result, 25 Hz power systems shrank and ...” in 📘 Physics if you're in doubt about the correctness of the answers or there's no answer, then try to use the smart search and find answers to the similar questions.