A 4-m * 5-m * 6-m room is to be heated by a base-board resistance heater. It is desired that the resistance heater be able to raise the air temperature in the room from 5 to 25°C within 17 min. Assuming no heat losses from the room and an atmospheric pressure of 100 kPa, determine the required power of the resistance heater. Assume constant specific heats at room temperature.

+3
Answers (1)
  1. 26 March, 12:50
    0
    Answer:2.11kW

    Explanation:

    1. V = 4x5x6 = 120m3

    2. M = p1V / RT1 = 100kpa x 120m3 / 0.287 kpa. m3/kg. k (273+5)

    M = 150.40kg

    3. Wein Delta t = MCvavg (T2-T1)

    = 150.44 x 0.718 x (25-5) / 17 x 60

    = 2159.44/1020 = 2.117kW
Know the Answer?
Not Sure About the Answer?
Find an answer to your question ✅ “A 4-m * 5-m * 6-m room is to be heated by a base-board resistance heater. It is desired that the resistance heater be able to raise the air ...” in 📘 Physics if you're in doubt about the correctness of the answers or there's no answer, then try to use the smart search and find answers to the similar questions.